XLPE Insulated Power Cable

Home » Products » Wire and Cables » XLPE Insulated Power Cable
XLPE Insulated Power Cable

XLPE insulated power cable is used to transmit and distribute power for the power transmission and distribution system of 35kV or lower. It is generally applied in the fields of power, construction, mine, metallurgy, petrochemical industry and communication. It completely replaces the oil immersed paper insulated power cable and partiallyreplaces the PVC insulated power cable.

Construction from the Inner Part to the Exterior Part of the XLPE Insulated Power Cable
Copper or aluminum conductor
XLPE insulation
Copper tape or copper wire screen
Galvanized steel wire or tape armored
PVC or PE sheath

Type Name Main Application
Cu core Al core
YJV
YJY
YJLV
YJLV
XLPE insulated, PVC or PE Sheathed Power Cable For laying indoor, tunnel, channel and underground. Unable to bear external mechanical force, but bear the traction force during laid
YJV22
YJV22
YJLV22
YJV22
XLPE Insulated, Steel Tape Armored, PVC or PE Sheathed Power Cable For laying indoor, tunnel, channel and underground. Able to bear external mechanical force, but unable to bear large pulling force
YJV32
YJV32
YJLV32
YJLV32
XLPE Insulated, Fine Steel Wire Armored, PVC or PE Sheathed Power Cable For laying in shaft with large difference of level. Able to bear external mechanical force and moderate pulling force
YJV42 YJV42 YJLV42 YJLV42 XLPE Insulated, Thick Steel Wire Armored, PVC or PE Sheathed Power Cable Able to bear positive pressure and pulling force

Note: "ZR-" includes ABC three kinds of flame retardent cables, which are respectively indicated in "ZRA-" or "ZRB-" "ZRC-". For example: "ZRB-YJV", "ZRA-YJV22".

Rated Voltage, No. of Core and Range of Sectional Area

Rated voltage (kv)
Sectional area (mm2)
No. of core
1st class 0.6/1 1.8/3 3.6/6 6/10 8.7/15 12/20 18/30 21/35
2nd class 1/1 3/3 6/6 8.7/10 12/15 18/20 - 26/35
1 Core
1.5-800 25-800 25-1200 25-1200 35-1200 50-1200 50-1200 50-1200
2 Core
1.5-185 25-185





3 Core
1.5-400 25-400 25-400 25-400 35-400 50-400 50-400 50-400
4 Core
2.5-400 25-400





5 Core
2.5-400 25-400





Main Technical Quota

1. DC resistance: conductor resistance of finished cable at 20℃ per kilometer is not more than the following values.

Nominal section area (mm2) 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800
Copper core 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 0.0221
Aluminum core 18.1 12.1 7.41 4.61 3.08 1.91 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.778 0.0605 0.0469 0.0367

2. Voltage Test and Partial Discharge Test

Rate voltage Uo (kv)
Item
0.6/1 1.8/3 3.6/6 6/6 6/10 8.7/10 8.7/15 12/20 18/20 18/30 21/35 26/35
Voltage Test voltage 3.5 6.5 12.5 21 30.5 42 63 73.5 91
Test time 5 5 5 5 5 5 5 5 5
Partial discharge test Test voltage - - 6.2 10.4 15.1 20.8 31.1 36.3 45
Discharge capacity - - 10 10 10 10 10 10 10

Package
The insulated power cable comes indrums or coils.

Tong-Da is an experienced XLPE insulated power cable manufacturer and supplier in China. In order to satisfy customers' various demands, we also provide PVC insulated wire, galvanized steel wire, galvanized steel strand, PVC insulated power cable, all aluminium conductor, ACSR, etc.